Using an older 200A breaker panel on a 60A feeder circuit from house?Grounding requirements for main panel...

Offset in split text content

Rendered textures different to 3D View

Air travel with refrigerated insulin

Trouble reading roman numeral notation with flats

Why doesn't Gödel's incompleteness theorem apply to false statements?

Put the phone down / Put down the phone

Highest stage count that are used one right after the other?

If the Dominion rule using their Jem'Hadar troops, why is their life expectancy so low?

Is there a distance limit for minecart tracks?

Why didn’t Eve recognize the little cockroach as a living organism?

Calculate Pi using Monte Carlo

Why didn't Voldemort know what Grindelwald looked like?

Should a narrator ever describe things based on a character's view instead of facts?

What (if any) is the reason to buy in small local stores?

Make a Bowl of Alphabet Soup

A seasonal riddle

Can a Knock spell open the door to Mordenkainen's Magnificent Mansion?

categorizing a variable turns it from insignificant to significant

Travelling in US for more than 90 days

Are hand made posters acceptable in Academia?

What is the tangent at a sharp point on a curve?

Recursively move files within sub directories

Is there any common country to visit for persons holding UK and Schengen visas?

Extract substring according to regexp with sed or grep



Using an older 200A breaker panel on a 60A feeder circuit from house?


Grounding requirements for main panel and subpanelUsing a 100A main breaker in a 200A panelHow should I wire a subpanel for a tiny house?Loads for sub panels from 150A split-bus main panelHow do I wire up a shed for 60A service today with the ability to grow later?Best choice for sub-panel and circuits for basementcan I turn a spa panel box into a circuit breaker boxIs there is a Standard on how much main service panel / main circuit breaker amps should be?Adding subpanel to a shedCan a sub-panel have a larger main breaker than the feeder breaker in the main panel?













1















I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.










share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





















  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago


















1















I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.










share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





















  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago
















1












1








1








I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.










share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.







circuit-breaker subpanel






share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question






New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked 4 hours ago









Charles LemonCharles Lemon

62




62




New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.













  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago





















  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago



















Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

– manassehkatz
4 hours ago





Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

– manassehkatz
4 hours ago













The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

– Charles Lemon
4 hours ago





The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

– Charles Lemon
4 hours ago













Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

– manassehkatz
4 hours ago





Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

– manassehkatz
4 hours ago




1




1





Yep - If I need to buy a few new breakers, that's fine.

– Charles Lemon
4 hours ago





Yep - If I need to buy a few new breakers, that's fine.

– Charles Lemon
4 hours ago




1




1





@manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

– Harper
1 hour ago







@manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

– Harper
1 hour ago












1 Answer
1






active

oldest

votes


















4














You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






share|improve this answer























    Your Answer








    StackExchange.ready(function() {
    var channelOptions = {
    tags: "".split(" "),
    id: "73"
    };
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function() {
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled) {
    StackExchange.using("snippets", function() {
    createEditor();
    });
    }
    else {
    createEditor();
    }
    });

    function createEditor() {
    StackExchange.prepareEditor({
    heartbeatType: 'answer',
    autoActivateHeartbeat: false,
    convertImagesToLinks: false,
    noModals: true,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    imageUploader: {
    brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
    contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
    allowUrls: true
    },
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    });


    }
    });






    Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.










    draft saved

    draft discarded


















    StackExchange.ready(
    function () {
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f160204%2fusing-an-older-200a-breaker-panel-on-a-60a-feeder-circuit-from-house%23new-answer', 'question_page');
    }
    );

    Post as a guest















    Required, but never shown

























    1 Answer
    1






    active

    oldest

    votes








    1 Answer
    1






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes









    4














    You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






    share|improve this answer




























      4














      You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






      share|improve this answer


























        4












        4








        4







        You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






        share|improve this answer













        You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered 4 hours ago









        Ed BealEd Beal

        34.2k12148




        34.2k12148






















            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.










            draft saved

            draft discarded


















            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.













            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.












            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.
















            Thanks for contributing an answer to Home Improvement Stack Exchange!


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.




            draft saved


            draft discarded














            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f160204%2fusing-an-older-200a-breaker-panel-on-a-60a-feeder-circuit-from-house%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown





















































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown

































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown







            Popular posts from this blog

            Why do type traits not work with types in namespace scope?What are POD types in C++?Why can templates only be...

            Will tsunami waves travel forever if there was no land?Why do tsunami waves begin with the water flowing away...

            Simple Scan not detecting my scanner (Brother DCP-7055W)Brother MFC-L2700DW printer can print, can't...